206 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Menu The specific configuration area will activate in the Settings - Modules - Ekip Measuring menu if the
Measurement module is detected correctly by Ekip Touch.
The following parameters can be configured in this menu:
Parameter
Voltage Transf.
Un Setting Mode
Rated voltage
Primary voltage
Secondary voltage
Positive Power flow
Neutral connection
When Un Setting Mode is set according to Table the voltage parameters can have the following values:
Parameter
Rated voltage
Primary voltage
Secondary voltage
Description
Selects the presence or absence of the external transformer Absent
Selects the rated voltage value selection mode:
• Table: value editable in preset steps
• Volt: value editable within the range in 1 V steps
Defines rated voltage Un.
Available in the absence of a transformer; defines rated
voltage Un.
The value is given in absolute value (Volts), editable within
the 100 V to 690 V range in steps which depend on the Un
Setting Mode parameter setting.
Available in the presence of a transformer; defines rated
voltage Un of the installation.
The value is expressed in absolute value (volt) and can be set
within the 100 V to 1150 V range, in steps that depend on the
Un Setting Mode parameter setting.
Available in the presence of a transformer; defines the
secondary voltage of the transformer.
The value is expressed in absolute value (volt) and can be set
within the 100 V to 230 V range, in steps that depend on the
Un Setting Mode parameter setting.
Defines the power flow required for D protection; there are 2
options available (page#s#76):
• High → Low: power flows from high terminals to low
terminals (load connected low)
• Low → High, power flows from low terminals to high
terminals (load connected high).
Available with 3P CB; allows the presence of the external
Neutral to be enabled.
NOTE: presence of the neutral activates phase voltage
measurement
Voltage values with adjustment in steps
100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240
V, 277 V, 347 V, 380 V, 400 V, 415 V, 440 V, 480 V,
500 V, 550 V, 600 V, 660 V, 690 V
100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240
V, 277 V, 347 V, 380 V, 400 V, 415 V, 440 V, 480 V,
500 V, 550 V, 600 V, 660 V, 690 V, 910 V, 950 V,
1000 V, 1150 V
100 V, 110 V, 115 V, 120 V, 200 V, 230 V
ABB | SACE Emax 2
Default
Table
400 V
400 V
100 V
Bottom →
Top
Absent
Internal electronic accessories
2 - Measurement