Swells Certain counters relating to swells are available in the Counters - Day - 1 and Counters - Cumulative
128 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Counters (Sags
Description
Middle)
Last time stamp
Date and time of last recording of the Sags Middle counter
Sags Middle
Value of last sag below the Sags Middle [V] threshold
Duration of last sag below the Sags Middle [ms] threshold
Sags Long
Actual number of S.
Sags Middle count of the current day
Actual [day -2 ... day -7]
Sags Middle count of the last seven days of activity, calculated using the
number of S.
internal clock of the unit
Counters (Sags
Description
Middle)
Last time stamp
Date and time of last recording of the Sags Long counter
Sags Middle
Value of last sag below the Sags Long [V] threshold
Duration of last sag below the Sags Long [ms] threshold
Sags Long
Actual number of S.
Sags Long count of the current day
Actual [day -2 ... day -7]
Sags Long count of the last seven days of activity, calculated using the
number of S.
internal clock of the unit
submenus:
Counters (Sags
Description
Middle)
Counts the number of times that any line-to-line voltage exceeds the V
Swells Short
swell Th Short threshold for longer than V swell dur Short
Counts the number of times that any line-to-line voltage exceeds the V
Swells Long
swell Th Long threshold for longer than V swell dur Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE: since an event may fall under more than one category, only the counter of the main
type (long > short) is increased
Additional List
Counters (Swells
Description
Short)
Last time stamp
Date and time of last recording of the Swells Short counter
Value of last swell above Swells Short [V] threshold
Last value
Last duration
Duration of last swell above Swells Short [ms] threshold
Actual number of S.
Swells Short count for the current day
Actual [day -2 ... day -7]
Swells Short count of the last seven days of activity, calculated using the
number of S.
internal clock of the unit
Counters (Swells
Description
Long)
Last time stamp
Date and time of last recording of the Swells Long counter
Value of last swell above Swells Long [V] threshold
Last value
Last duration
Duration of last swell above Spikes [ms] threshold
Actual number of S.
Swells Long count for the current day
Swells Long count of the last seven days of activity, calculated using the
Actual [day -2 ... day -7]
number of S.
internal clock of the unit
ABB | SACE Emax 2
Ekip Touch - Measurements
5 - Network Analyzer