Measurement - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

2 - Measurement

Presentation Two Measurement modules are available:
Measurement performance The measurement performance provided when the Measurement modules are installed (described on
Configurations available Both modules can be ordered with different connection configurations:
Electrical characteristics The Measurement modules function correctly in the electrical conditions described on page 20.
Isolation transformer The isolation transformer must conform to standard IEC 60255-27 and possess the following
205 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
• Measurement enabler installed by default on Ekip Touch and enabled in the presence of the
Measuring Measurements package (enabling can be obtained both at the time the circuit-breaker
is ordered or at a later date, via Market Place)
• Measurement enabler with voltage socket is installed by default on Ekip Hi-Touch, Ekip G Touch
and Ekip G Hi-Touch; can be installed in conjunction with Ekip Touch if requested when circuit-
breaker is ordered
Both modules measure voltages, frequencies, power and energy values; in addition, the Measurement
enabler with voltage socket module allows:
• the Trip unit to be supplied directly by the voltage sockets to which it is connected
• management of the synchronism function when the Ekip Synchrocheck module is installed (see
chapter dedicated to Ekip Synchrocheck from page 247).
page 117), are more accurate when the Class 1 Power & Energy Metering package is present (described on
page 120.
• connections to internal terminals or in an external terminal box
• connections to the upper or lower terminals of the poles on the basis of the expected power flow
• with normal or reverse pole order
For full details about ordering and the connections, consult technical catalog
wiring diagrams 1SDM000091r0001.
Installations with up to 1200 VAC line-to-line voltage can be connected and configured in the presence of
connections to external sockets and an isolation transformer.
characteristics:
Characteristics
Description
• Accuracy class: ≤ 0,2
• Performance: ≥ 10 VA
• Overload: 20 % permanent
• Insulations: 4 kV between inputs and outputs, 4 kV between shield and
Electrical
outputs, 4 kV between shield and inputs
• Frequency: Fn +-10%
• Primary voltage: 100 to 1200 V (nominal, to be configured via menu)
• Secondary voltage: 100 to 230 V (nominal, to be configured via menu)
ABB | SACE Emax 2
1SDC200023D0906