Mitsubishi Electric GT11 User Manual page 340

Graphic operation terminal
Hide thumbs Also See for GT11:
Table of Contents

Advertisement

Error
Error message
code
Communication channel not set.
480
Set channel number on Utility.
Warning! Built-in battery voltage
500
is low.
510 Clock data input out of range
Unnecessary file deleted to
522
create new file.
Device writing error.
524
Correct device.
Unable to read/write alarm log
525
files under different projects.
535 Cannot open image file.
Image file error or invalid file
536
format.
550 Invalid key code
570 Recipe device points too large.
Capacity shortage of user
571
memory (RAM)
18 - 6
18.2 List of Error Message/System Alarm
One or more channel for PLC and host (microcomputer) connection (Ch.1
to 5) is not allocated by drawing software or utility.
Set the channel by drawing software or utility.
The voltage of the GOT built-in battery is decreased.
Replace the GOT built-in battery.
The value that is input as clock data is out of the input enabled range.
In this case, the input value is not accepted.
Confirm the input range of the value to be input as clock data, and input
the proper value again.
Cancelled the file of different contents and created a new file.
Note that the old file is cancelled and the new file is created if the file of
the same name with different contents exists when creating files.
When writing in the device, error occurred.
Correct the device.
Unable to read the alarm log file saved by the different project.
Confirm where to store the alarm log file and alarm log file.
• No CF card is installed in the drive or the access switch is turned on.
1. Install a recording medium in the specified drive.
2. Turn the access switch on.
• The specified file is not found in the card.
3. Add the image file or change the image file name to a correct one.
There is an error in the image file data or the image file format is not
supported.
Change to the correct image file.
The key code input execution trigger was ON with the non-target key code
set in the key code storage device.
Confirm the key code supported by the object where error occurs.
The number of the set points of the recipe device exceeds the specified
range.
Put the number of the set points of the recipe device within the specified
range.
There is no empty area/space in D drive.
If the alarm log file located in the D drive needs to be backed up, copy it to
the CF card with the utility and then format the D drive.
If the recipe function is used to read devices, format the D drive and then
read again to create the recipe data.
Action

Advertisement

Table of Contents
loading

This manual is also suitable for:

Got1000