Error message
**KS over
**KP over
Not available for QnACPU.
Set the PLC No.
The keyword is not input.
Set the PLC No.
The PLC parameter was
changed.
Read the ladder monitor again.
The PLC parameter was
changed.
Restart the GOT system.
The PLC program was edited.
Read the ladder monitor again.
14 - 80
14.3 MELSEC-A List Editor
14.3.28 Error messages and corrective actions
Description
The value exceeding the range of the program capacity
by **K steps was attempted to be set.
The value exceeding the range of the file register
capacity by **K points was attempted to be set.
The CPU at the list edit destination is QnACPU.
The "GO" key was pressed without input of the keyword
on the keyword input screen.
The PLC parameter exceeding the file (R)
register capacity was set.
The capacity of the file (R) register was set.
Edit the PLC program.
Corrective action
Reduce the program capacity by **K steps for
setting.
The value exceeding the range of the file
register capacity by **K points was attempted
to be set.
Set the PLC number and change the station for
access.
Set the PLC number and change the station for
list edit. Or select the same station and input
the keyword.
Restart the GOT system if required.
Read the ladder monitor on the PLC again if
required.
Read the ladder monitor on the PLC again if
required.