ABB i-bus KNX Product Manual page 236

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX GROUP OBJECTS
No.
Function
127
Status information
This group object can be used to output status information about the output's operating state.
The sending behavior can be defined in the Send value of group object parameter. If the "On request" or "After change or on request" option is selected,
the status is sent each time a bit value is changed.
Bit 0: Manual operation
Telegram value:
1 = active
0 = inactive
Bit 1: Disable
Telegram value:
1 = active
0 = inactive
Bit 2: Forced operation
Telegram value:
1 = active
0 = inactive
Bit 3: Safety priority 1
Telegram value:
1 = active
0 = inactive
Bit 4: Safety priority 2
Telegram value:
1 = active
0 = inactive
Bit 5: Safety priority 3
Telegram value:
1 = active
0 = inactive
Bit 6: Staircase lighting Permanent ON
Telegram value:
1 = active
0 = inactive
Bit 7: i-bus® Tool
Telegram value:
1 = active
0 = inactive
For more information → Code table for 8-bit status byte (Switch), Page 251.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator
Parameter window Switch Actuator A \ Parameter window Basic settings \ Parameter Parameter setting \ Option Individual \ Parameter Enable
group object "Status information" \ Option Yes
128
Flashing
This group object can be used to activate the function Flashing . The telegram value that activates the function Flashing can be defined in the parameter
Flashing if group object Flashing equals.
For more information → Function Flashing, Page 95.
Note
Only a limited number of switching operations can be performed per minute and relay. Frequent switching can cause a switching delay. Refer to the
Technical data for more information.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Flashing
129
Scene 1...64
This group object can be used to send a scene telegram. The scene telegram includes the scene number and information about whether the scene is re-
trieved or the relay switching state is saved in the scene.
Assignment to a scene number can be performed in the Parameter window Scene assignment, and this applies only to the output in which the scene as-
signment was set.
Telegram value:
0 ... 63 = retrieve scene x (x = 1 ... 64)
128 ... 191 = save scene x (x = 1 ... 64)
More information → Code table 8-bit scene, Page 254.
Note
With the priorities of the safety functions, a change in the group object does not necessarily result in a changed contact position.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Scenes \ Option Yes
Group Object Name
Channel A: Switch
Channel A: Switch
Channel A: Switch
Data Point Type Length
nonDPT
1 byte
DPT 1.001
1 bit
DPT 18.001
1 byte
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 236
Flags
C R
T
C
W
C
W