ABB i-bus® KNX PARAMETERS
7.9.5.1.5
DEPENDENT PARAMETER
Forced operation (1 bit / 2 bit)
This parameter can be used to define whether 1-bit or 2-bit forced operation is used.
More information → Forced operation, Page 79.
When the function Forced operation is active, the output can no longer be operated via other group
objects or manual operation until forced operation has been canceled.
Higher-priority safety functions will continue to run.
Options
Deactivated
Activated 1 bit – 0 active
Activated 1 bit – 1 active
Activated 2 bit
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual
7.9.5.1.5.1
DEPENDENT PARAMETER
Position height (0 % = top; 100 % = bottom)
This parameter can be used to define the position to which the blind/shutter is moved.
The position will be approached only with deactivated automatic sun protection.
Options
0 ... 100 %
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual  \ Parameter
Forced operation (1 bit / 2 bit) \ Option Activated 1 bit – 0 active
Note
The function Forced operation is deactivated.
1-bit forced operation is used and is activated when the value 0 is received. The group object Forced
operation, 1-bit is enabled.
1-bit forced operation is used and is activated when the value 1 is received. The group object Forced
operation, 1-bit is enabled.
2-bit forced operation is used. The group object Forced operation, 2-bit is enabled. The value of the
group object determines the switching state.
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
Forced operation active ON
Forced operation active OFF