ABB i-bus® KNX PARAMETERS
7.3.7
Enable central Scene group object
This parameter can be used to enable the central Scene group object Scene 1 ... 64 . All outputs assigned
to the scene can be activated together with the central Scenes group object.
Observe the maximum number of switching cycles per minute when using the central Scenes group ob-
ject → Technical data.
Options
No
Yes
7.3.8
Enable group object "In operation"
This parameter can be used to enable the group object In operation . The group object reports the pres-
ence of the device on the ABB i-bus® KNX and can be monitored by an external device. If a telegram is not
received, the device may be defective or the bus cable to the transmitting device may be interrupted.
The dependent parameter Sending cycle can be used to set the cycle during which the group object
sends a telegram.
Options
No
Yes, send value 0 cyclically
Yes, send value 1 cyclically
7.3.8.1
DEPENDENT PARAMETER
Sending cycle
This parameter can be used to define the cycle during which group object In operation sends a tele-
gram.
Options
00:00:01 ... 00:10:00 ... 18:12:15 hh:mm:ss
Condition for visibility:
Parameter window Device settings \ Parameter Enable group object "In operation" \ Option Yes, send
value 0 cyclically
The group object is not enabled.
The group object is enabled.
The group object is not enabled.
The group object is enabled and cyclically sends the value 0.
Sending cycle
The group object is enabled and cyclically sends the value 1.
Sending cycle
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 110