ABB i-bus® KNX PARAMETERS
—
7.9.5.1.6.2
DEPENDENT PARAMETER
Position slat (0 % = open; 100 % = closed)
This parameter can be used to define the position to which the blind/shutter slats are moved.
The position will be approached only with deactivated automatic sun protection.
This parameter is available only in Operating mode Blind/shutter control with slat adjustment .
Options
0 ... 100 %
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual \ Parameter Posi-
tion on cancellation of weather alarm, disabling and forced operation \ Option Individual position
—
7.9.5.1.7
DEPENDENT PARAMETER
Automatic sun protection on cancellation of weather alarms, disabling and forced operation
This parameter can be used to define whether the Automatic sun protection function is deactivated af-
ter the cancellation of weather alarms or the Disable and Forced operation functions.
This parameter is visible only if, in the Parameter window Functions, the following option was set for
the parameterEnable function Automatic sun protection: Yes .
Options
No
Yes
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual
—
7.9.5.1.8
DEPENDENT PARAMETER
Order of priority of weather alarm, disabling and forced operation
This parameter can be used to define the order of priority of the safety functions. If more than one
safety function is active at the same time, only the safety function with the highest priority is executed.
Options
1.Weather alarm - 2.Disable - 3.Forced operation
1.Weather alarm – 2.Forced operation – 3.Disable
1.Disable – 2.Weather alarm – 3.Forced operation
1.Disable – 2.Forced operation – 3.Weather alarm
1.Forced operation - 2.Weather alarm - 3.Disable
1.Forced operation - 2.Disable - 3.Weather alarm
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual
Note
Note
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 170