ABB i-bus® KNX PARAMETERS
7.10.5.1.3
DEPENDENT PARAMETER
Disable delay for switching ON and OFF via group object
This parameter can be used to define whether the function Delay for switching ON and OFF can be dis-
abled via the group object Disable delay for switching ON and OFF . If the function Delay for switching
ON and OFF is disabled, the switch-on command is forwarded without time function in the function
chain and the output reacts according to its parameterization. Disabling remains in effect after a down-
load.
Options
No
Yes
Condition for visibility:
Parameter window Delay for switching ON and OFF \ Parameter Parameter setting \ Option Individual
7.10.5.1.3.1
DEPENDENT PARAMETER
Disable delay for switching ON and OFF after bus voltage recovery
This parameter can be used to define whether the delay for switching ON and OFF is disabled after bus
voltage recovery.
Options
No
Yes
Condition for visibility:
Parameter window Delay for switching ON and OFF \ Parameter Parameter setting \ Option Individual  \
Parameter Disable delay for switching ON and OFF via group object \ Option Yes
The Delay for switching ON and OFF cannot be disabled via the group object Disable delay for
switching ON and OFF .
The Delay for switching ON and OFF can be disabled via the group object Disable delay for switching
ON and OFF ; the group object is enabled.
Disable delay for switching ON and OFF after bus voltage recovery
The delay for switching ON and OFF is not disabled after bus voltage recovery.
The delay for switching ON and OFF is disabled after bus voltage recovery.