ABB i-bus® KNX PARAMETERS
7.6.1.14
DEPENDENT PARAMETER
Result if lower threshold is dropped below
This parameter can be used to define the result of the function Threshold when the value received at the
threshold input falls below the lower threshold. The result can be linked with any output within the de-
vice or output on the group object Result .
Options
Unchanged
1
0
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
7.6.1.15
DEPENDENT PARAMETER
Min. duration of the undershoot
This parameter can be used to define how long the value received at the threshold input must fall below
the threshold before the result of the function Threshold is updated.
Options
00:00:00 ... 18:12:15 hh:mm:ss
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
7.6.1.16
DEPENDENT PARAMETER
Update result after each overshoot/undershoot
This parameter can be used to define whether the result of the function Threshold is updated whenever
the value received at the threshold input exceeds or falls below a threshold.
Options
No
Yes
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
The result of the function Threshold remains unchanged.
The result of the function Threshold is 1.
The result of the function Threshold is 0.
The result of the function Threshold is updated only if the received value triggers a result change.
The result of the function Threshold is updated when the received value exceeds or falls below a
threshold.