ABB i-bus® KNX PARAMETERS
7.9.6.1.4.1
DEPENDENT PARAMETER
Position height (0 % = top; 100 % = bottom)
This parameter can be used to define the position to which the blind/shutter is moved.
The position will be approached only with deactivated automatic sun protection.
Options
0 ... 100 %
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual  \ Pa-
rameter Position for sun = 1 (sun) \ Option Individual position
7.9.6.1.4.2
DEPENDENT PARAMETER
Position slat (0 % = open; 100 % = closed)
This parameter can be used to define the position to which the blind/shutter slats are moved.
The position will be approached only with deactivated automatic sun protection.
This parameter is available only in Operating mode Blind/shutter control with slat adjustment .
Options
0 ... 100 %
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual  \ Pa-
rameter Position for sun = 1 (sun) \ Option Individual position
7.9.6.1.5
DEPENDENT PARAMETER
Delay for sun = 1
This parameter can be used to set the delay time after which the blind/shutter moves into position
when the sun shines. This can serve to avoid unnecessary position changes due to brief periods of sun-
shine on cloudy days.
Options
00:00:00 ... 01:40:00 hh:mm:ss
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual
Note
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 175