ABB i-bus® KNX PARAMETERS
7.9.5.1.6
DEPENDENT PARAMETER
Position on cancellation of weather alarm, disabling and forced operation
This parameter can be used to define the blind/shutter reaction after cancellation of weather alarms or
the functions Disable and Forced operation .
Options
No reaction
Up
Down
Stop
Scene assignment
Individual position
Refreshed KNX state
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual
7.9.5.1.6.1
DEPENDENT PARAMETER
Position height (0 % = top; 100 % = bottom)
This parameter can be used to define the position to which the blind/shutter is moved.
The position will be approached only with deactivated automatic sun protection.
Options
0 ... 100 %
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual  \ Parameter Posi-
tion on cancellation of weather alarm, disabling and forced operation \ Option Individual position
If the blind/shutter is moving, it will continue until reaching the target position. If the blind/shutter is
at rest, its position will remain unchanged.
The blind/shutter moves to the upper end position
The blind/shutter moves to the lower end position
If the blind/shutter is moving, it will be stopped. If the blind/shutter is at rest, its position will remain
unchanged.
The scene assigned to the Shutter Actuator output pair is performed.
The required positions of the blind/shutter and slats (depending on operating mode) can be defined.
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
The blind/shutter moves to the position defined by the refreshed KNX state. More information →
Refreshed KNX state, Page 83.
Telegrams that were received during an active weather alarm or the functions Disable and Forced
operation on the group objects Move blind/shutter Up-Down and Slat adjustment/stop Up-Down .
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 169