ABB i-bus KNX Product Manual page 180

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.9.7.1.1.1
DEPENDENT PARAMETER
Send value of group object
This parameter can be used to define whether the value of the group object will be sent to the
ABB i-bus® KNX.
Options
No, update only
After change
On request
After change or on request
Condition for visibility:
Parameter window Status messages \ Parameter Parameter setting \ Option Individual  \ Parameter En-
able group objects "Status Height/Slat" \ Option Yes
7.9.7.1.2
DEPENDENT PARAMETER
Enable group objects "Status Upper/Lower end pos."
This parameter can be used to enable the group objects Status Upper end position and Status Lower
end position .
The output sends the value 1 on these group objects when the blind/shutter is in the respective end po-
sition. The blind/shutter is in an intermediate position if the value 0 is sent on both group objects.
These communication objects can be used for mutual interlocking of individual outputs by means of a
logical connection.
Example:
An awning must not be moved when the window is open. Conversely, a drive must not open the win-
dow when the awning is down.
Options
No
Yes
Condition for visibility:
Parameter window Status messages \ Parameter Parameter setting \ Option Individual
The value of the group object is updated but not sent.
The value of the group object is sent after every change.
The value of the group object is sent on request. A request can be triggered by sending the value 0 or
1 on the group object Request status values .
The value of the group object is sent after a change or on request. A request can be triggered by
sending the value 0 or 1 on the group object Request status values .
The group objects will not be enabled.
The group objects will be enabled.
Send value of group object
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 180