UPS5000-E-(40 kVA-320 kVA)
User Manual
3.2.12 Connecting Battery Cables
Context
Procedure
Step 1 (Optional) Connect the cable between the BCB box and intelligent battery detector.
For the connection methods, see the manuals for these components.
Step 2 Connect the wires of the battery cable to positive and negative battery terminals and terminal
N on the UPS cabinet, as shown in
UPS5000-E-200K-F200),
the UPS5000-E-320K-F320T).
Issue 10 (2015-09-15)
If an output PDC is used, see the PDC-0630ACV4OUA Power Distribution Unit User Manual to
connect cables between the output PDC and the UPS.
The battery string voltage may cause serious injury. Observe safety precautions when
connecting cables.
Ensure that cables are correctly connected between battery strings and the battery switch,
and between the battery switch and the UPS.
Figure 3-53
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 3-52
(for the UPS5000-E-120K-F120 and
(for the UPS5000-E-320K-F320), and
3 Installation
Figure 3-54
(for
81