UPS5000-E-(40 kVA-320 kVA)
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0043-2
0043-3
0043-4
0047-1
0060-4
0061-7
0564-1
Issue 10 (2015-09-15)
Alarm
Severit
Name
y
Not ready
Critical
Inverter
Critical
abnormal
Inverter
Minor
alarm
Overload
Critical
timeout
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
abnormal.
The fan
monitorin
g cable
for the
power
module is
abnormal.
The fan is
Check the fan or replace the bypass
faulty.
unit or module.
1. Replace the fan.
The fan is
faulty.
2. Check the fan monitoring cable.
The fan
monitorin
g cable is
faulty.
The ready
Turn on the ready switch.
switch is
OFF.
1. Check load cable connections.
A load
short-circ
2. If load cable distributions are
uit occurs.
normal, replace the power
module.
A short
circuit
occurs
inside the
module.
The fault
seldom
occurs.
1. If not all modules generate the
The bypass
alarm, start the UPS and transfer
waveform is
it to normal mode and replace
abnormal.
the faulty module.
2. If all modules generate the
alarm, open the bypass input
circuit breaker. After the
inverter relay is closed, close
the bypass input circuit breaker
10 seconds later.
1. Check that there is no overload.
The load
is
2. Check that the module power is
excessive.
not derated due to a fan fault.
3. If the alarm persists, replace the
Derating
B Alarm List
233