UPS5000-E-(40 kVA-320 kVA)
User Manual
Port
EPO
SWIT
CH
STAT
US
SWIT
CH
STAT
US
-
NO is short for normally open, and NC is short for normally closed.
Issue 10 (2015-09-15)
Silk Screen
Description
STA
Monitors the battery switch
DRV
Controls the trip of the
battery switch in the BCB
box
0 V
Secondary side ground
NO
EPO port
12 V
+12 V
NC
EPO port
12 V
+12 V
OUT
Monitors the UPS output
circuit breaker on the output
power distribution cabinet
(PDC)
0 V
Secondary side ground
MT
Monitors the maintenance
circuit breaker on the output
PDC
0 V
Secondary side ground
BP
Monitors the bypass input
circuit breaker on the input
PDC
0 V
Secondary side ground
SPD
Monitors the input AC SPD
0 V
Secondary side ground
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Overview
Status
Status:
Connected: battery switch ON
Disconnected: battery switch
OFF
The initial status is Disconnected.
Voltage:
0 V: battery switch not tripped
12 V: battery switch tripped
The initial port voltage is 0 V.
The initial status is Disconnected.
If the normally open (NO) port is
connected to the EPO_12V port,
EPO is triggered.
The initial status is Connected. If
the normally closed (NC) port is
disconnected from the EPO_12V
port, EPO is triggered.
Status:
Disconnected: circuit breaker
OFF
Connected: circuit breaker ON
The initial status is Connected.
Status:
Disconnected: circuit breaker
ON
Connected: circuit breaker
OFF
The initial status is Disconnected.
Status:
Disconnected: circuit breaker
OFF
Connected: circuit breaker ON
The initial status is Connected.
Status:
Disconnected: SPD disabled
Connected: SPD enabled
The initial status is Connected.