Huawei UPS5000-E-12 User Manual page 138

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 4-49 Dry Contacts screen 7
Issue 10 (2015-09-15)
MUE05A connection
MUE05A connection status. Independent input signals can be enabled only when this
parameter is set to Enable.
Batter ground fault [BTG]
Enable or disable the battery grounding failure detection.
D.G. connection [GEN]
Enable or disable D.G. connection detection.
BCB connection [OL]
Enable or disable BCB connection detection.
Batter breaker [STA]
Enable or disable battery circuit breaker monitoring.
PDC output breaker [OUT]
Enable or disable PDC output circuit breaker monitoring.
PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker monitoring.
BP/SYSMT Switch
If the BP/SYSMT switch is set to Enable, the port has dry contact signal access. How a
user uses the port depends on the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU bypass input switch or system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to Enable, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to Enable, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU input surge protector or system output switch.
MUE06A connection
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
129

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents