UPS5000-E-(40 kVA-320 kVA)
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0036-2
0037-1
0040-7
0043-1
Issue 10 (2015-09-15)
Alarm
Severit
Name
y
Battery
Warning
maintenanc
e reminder
Battery
Critical
undervoltag
e
Rectifier
Critical
abnormal
Fan
Critical
abnormal
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
threshold.
The
configure
d number
of
batteries
is less
than the
actual
number.
The actual
number of
batteries
does not
meet
requireme
nts.
The time for
Maintain the batteries.
maintenance
arrives.
1. Check whether the battery
The UPS
voltage is normal.
works
long in
2. Check whether the output is
battery
overloaded.
mode.
3. Check whether any battery is
damaged. If yes, replace the
The
battery.
charger is
faulty.
4. Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
1. Check that the air channel for
The fan
the module is free from
for the
blockage.
power
module is
2. Check whether the fan is
abnormal.
abnormal. Replace the power
module if the fan is faulty.
The air
channel of
the power
module is
obstructed
.
The fan
Replace the faulty power module.
for the
power
module is
B Alarm List
232