Huawei UPS5000-E-12 User Manual page 104

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
No.
04
05
06
07
08
09
10
11
12
13
After routing cables and checking cable connections, use fireproof mud to fill in the gap between the
cables and the cabinet, and reinstall the front panels on the power distribution subrack and top entry
cabinet.
Issue 10 (2015-09-15)
Item
Serial port connection (security
protection mechanism
supported)
Cable labels
Ground cable connections
Distances between cable ties
Cable connections
Live wire and neutral wire
connections
Input and output live wire phase
sequences
Battery cable connection
Operating environment
Copper busbar short circuit
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected Result
washers are flattened, prevent falling off and
safety accidents. Ensure that there is no
disconnection or potential risk.
Signal cables are connected properly and
securely.
Both ends of each cable are labeled. Labels
are easy to understand.
The ground cable is securely connected to the
equipment room ground bar. Measure the
resistance between the UPS ground cable and
the equipment room ground bar, which must
be less than 1 ohm.
Distances between cable ties are the same, and
no burr exists.
Cables are properly connected according to
wiring diagrams.
Input and output live wires and neutral wires
are correctly connected. Mains input terminals
1L1, 1L2, 1L3, and N, bypass input terminals
2L1, 2L2, 2L3, and N, and output terminals U,
V, W, and N are properly connected.
In single UPS mode, mains and bypass input
and output live wires are connected in a
correct sequence; in a parallel system, mains
and bypass input and output live wires are
connected in the same sequence for each UPS.
Check that the voltages on the positive and
negative battery terminals and battery N are
correct using a multimeter.
Clean the conductive air and other sundries.
Check that copper busbars are open-circuited
using a multimeter.
3 Installation