Battery Specifications; Output Electrical Specifications - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual

8.6 Battery Specifications

Item
Battery
voltage
Battery
monitoring
Battery
management
One-button
cold start
Battery string
sharing
Charge
voltage

8.7 Output Electrical Specifications

Item
Output
system
Voltage
Frequency
Total
harmonic
distortion
of output
voltage
(THDv)
Output PF
Transfer
time
Issue 10 (2015-09-15)
UPS5000-E-120K-F
120
360–552 V DC (30–46 batteries, 32 by default); 6% derated when 30
batteries are configured.
The BMU (optional) monitors batteries.
Intelligent battery management
In the case of a mains failure, batteries can start the UPS to power loads.
The UPSs connected in parallel can share battery strings. By default,
battery strings are not shared.
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
In monitoring and power versions earlier than V100R001C10SPC008 (software package version:
V100R001C10SPC700), the battery voltage is 360–480 V DC (30 to 40 batteries, 32 by default).
UPS5000-E-120K-F
120
Three-phase, five-wire
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
In normal mode, the mains frequency is synchronized with the bypass input
frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ± 0.25%).
< 1% (full linear load); < 3% (full non-linear load)
1
0 ms
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-2
UPS5000-E-3
00K-F200
20K-F320
UPS5000-E-20
UPS5000-E-32
0K-F200
0K-F320
8 Technical Specifications
UPS5000-E-3
20K-F320T
UPS5000-E-32