Huawei UPS5000-E-12 User Manual page 46

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Table 3-3
Table 3-3 Recommended cross-sectional areas for power cables
Item
M
Mains input
ai
current (A)
ns
Recom
L1
in
mended
pu
L2
cross-se
t
ctional
L3
area
2
(mm
)
N
B
Bypass input
yp
current (A)
as
Recom
L1
s
mended
in
L2
cross-se
pu
ctional
t
L3
area
2
(mm
)
N
O
Output current
ut
(A)
pu
Recom
U
t
mended
V
cross-se
ctional
W
area
2
(mm
)
N (If
the
volta
ge is
Issue 10 (2015-09-15)
The UPS can generate large leakage currents. A circuit breaker that provides leakage
current protection is not recommended.
If multiple UPSs are to be connected in parallel, input and output power cables for each
UPS should have the same length and specifications.
In
Table
3-3, the mains input power cable diameter of the UPS5000-E-240 kVA is less than
that of the UPS5000-E-200 kVA. The following describes the reason: Cables for the
UPS5000-E-(40 kVA-200 kVA) can be multi-core or single-core while those for the
UPS5000-E-(240 kVA-320 kVA) can only be single-core (single-core cables endure
currents better than multi-core cables).
lists the recommended cross-sectional areas for power cables.
UPS5000-E-120K-F120
40
80
120
kVA
kVA
kVA
71
142
213
4 x 16
4 x 50
4 x 95
61
122
182
4 x 16
4 x 35
4 x 70
61
122
182
4 x 16
4 x 35
4 x 70
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-200K-
UPS5000-E-320K-F320/UPS500
F200
0-E-320K-F320T
160
200 kVA
240 kVA
kVA
284
355
426
2 x (4 x
2 x (4 x
2 x (4 x
70)
95)
70)
(Cable
types are
different.
)
243
304
365
2 x (4 x
2 x (4 x
2 x (4 x
50)
70)
70)
243
304
365
2 x (4 x
2 x (4 x
2 x (4 x
50)
70)
70)
3 Installation
280 kVA
320 kVA
498
569
2 x (4 x
2 x (4 x
95)
120)
425
486
2 x (4 x
2 x (4 x
70)
95)
425
486
2 x (4 x
2 x (4 x
70)
95)
37