Installation time
A battery maintenance reminder is displayed when the maintenance time (counted from
the installation time) comes.
Maintenance period (d)
Interval for reminding users of battery maintenance.
Battery type
Set the battery type based on actual conditions. Currently, only lead-acid batteries are
supported.
Chg. cur. limiting coef. (C10)
Charging current limit, which is a multiple of the battery capacity. The value can be
0.05–0.15, 0.1 by default.
Cell float voltage (V/cell)
Set the float voltage. The value can be 2.23–2.27 V/cell, 2.25 V/cell by default. The
value is configurable in any mode.
Cell equalized volt. (V/cell)