Huawei UPS5000-E-12 User Manual page 247

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0342
0343
0340
0345
0335
0594-1
0095-1
0096-1
Issue 10 (2015-09-15)
Alarm
Severit
Name
y
Mains
Critical
input
breaker
open
BPM input
Critical
breaker
open
Maint.
Minor
breaker
closed
Battery
Critical
breaker
open
Generator
Warning
connected
Insufficient
Minor
redundant
racks
Insuffi.
Minor
redundancy
ECO volt.
Minor
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
ON.
The mains
Running status displayed. No
input circuit
suggested measures.
breaker is
OFF.
The bypass
Running status displayed. No
input circuit
suggested measures.
breaker is
OFF.
The
Running status displayed. No
maintenance
suggested measures.
circuit
breaker is
ON.
The battery
Running status displayed. See
circuit
details about how to handle other
breaker is
alarms.
OFF.
The generator
Running status displayed. No
is connected.
suggested measures.
1. Reduce the load.
The load
is
2. Decrease the configured number
excessive.
of redundant racks.
The
configure
d number
of
redundant
racks is
incorrect.
1. Reduce the load.
The load
is
2. Decrease the configured number
excessive.
of redundant modules.
The
configure
d number
of
redundant
modules
is
incorrect.
1. Check the bypass input voltage
The ECO
and frequency.
bypass
B Alarm List
238