UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 3-37 Routing power cables from the bottom of the cabinet
(1) Mains input
PE
(5) Mains input
N
(9) Bypass
input L3
(13) Output V
(17) Battery
input N
When you choose to route cables by drilling holes, drill holes on the bottom plate, and paste grommet
strip to the hole edge to protect cables. Then route cables through the holes, use fireproof putty to fill in
the gap between cables and the cabinet.
Step 4 Route the cables on the left of subracks along the left side of the cabinet and the cables on the
right side of subracks along the right side of the cabinet, and then bind the cables to the
cabinet, as shown in
Issue 10 (2015-09-15)
(2) Mains input L1
(6) Bypass input PE
(10) Bypass input N
(14) Output U
(18) Battery input
negative terminal
Figure
3-38.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(3) Mains input
(4) Mains input L3
L2
(7) Bypass
(8) Bypass input L2
input L1
(11) Output PE
(12) Output W
(15) Output N
(16) Battery input
positive terminal
3 Installation
70