UPS5000-E-(40 kVA-320 kVA)
User Manual
Step 2 Close the input surge protection circuit breaker on the input PDC.
If no input surge protection circuit breaker is configured, go to the next step. If the input surge protection
circuit breaker is not closed, an alarm is generated and a message is displayed to prompt you to close it.
Step 3 After the LCD starts, perform the following steps:
After you specify the settings, the Bypass mode and No battery alarms are displayed on the LCD.
The main buttons on the Settings Wizard screen are described as follows:
1.
2.
Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.
Issue 10 (2015-09-15)
If the UPS is starting for the first time, set the language, date and time, network
parameters, and system parameters on the Settings Wizard screen.
If this is not the first startup, retain the previous settings.
Tap Previous to return to the upper-level screen.
Tap Next to go to the next screen.
Tap Cancel to exit the Settings Wizard screen.
Various languages are available, such as Chinese and English. Press Down and Up to
view the language types, as shown in
Figure 5-3 Language screen
Tap Next on the Time screen, select a date format, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
5-3.
5 Operations
Figure
5-4.
151