UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 5-35 Turning off the maintenance bypass switch on the UPS5000-E-200 kVA
Step 2 Start the inverter by following
UPS.
----End

5.9 Performing EPO

Press the EPO switch connected to the dry contact card on the UPS or remove the 4-pin
terminal from the EPO port on the dry contact card, as shown in
transfers to the EPO state. An alarm is generated on the MDU and WebUI, as shown in
5-37
Issue 10 (2015-09-15)
This figure applies to the UPS5000-E-200 kVA.
After you turn on the EPO switch, the UPS supplies no power, and the loads shut down.
In maintenance bypass mode, the UPS still supplies power after you turn on the EPO
switch.
and
Figure
5-38.