3.1.4 Unpacking and Checking

Context
Issue 10 (2015-09-15)
UPS
Capacity
120 kVA
160 kVA
200 kVA
240 kVA
280 kVA
320 kVA
The input upstream circuit breakers recommended in
If multiple loads are connected, specifications for branch circuit breakers must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
Table 3-7
3 Installation
Specification
Manufactur
s
er
T3N250 TMD
R250 FF 3P
T3N250 TMD
R250 FF 3P
T5N400 TMA
R320 FF 3P
T5N400 TMA
R320 FF 3P
T5N400 TMA
R400 FF 3P
T5N400 TMA
R400 FF 3P
T5N630 TMA
R500 FF 3P
T5N630 TMA
R500 FF 3P
T5N630 TMA
R500 FF 3P
T5N630 TMA
R500 FF 3P
T6N630
PR221DS-LS/
I R630 FF 3P
T6N630
PR221DS-LS/
I R630 FF 3P
are for reference only.
41