Huawei UPS5000-E-12 User Manual page 166

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
Step 7 Ensure that the UPS transfers to normal mode. View the system running diagram to check that
the Bypass mode alarm disappears on the LCD. Check the UPS three-phase output voltage
and frequency by viewing the AC Output data on the LCD, as shown in
Figure
Issue 10 (2015-09-15)
Figure 5-11 Login
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
e.
On the homepage, choose Monitoring > Control, and click Inverter On. In the
displayed dialog box, click OK to start the inverter, as shown in
Figure 5-12 Starting the inverter
5-14. Use a multimeter to measure the three-phase output voltage and frequency.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Figure
5-12.
Figure 5-13
and
157

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents