Figure 5-45 Confirmation message
Figure 5-46 Security warning on the LCD
Step 4 Check that the load power is stable (overload due to transient surge may cause the UPS to
transfer to bypass mode), and click Yes.
Step 5 Set the Module cycle hiber. period (days) parameter to an integer ranging from 0 to 100.
The default value is 30. If the value is 0, the hibernation period is 2 minutes. That is, the
module starts automatically after 2-minute hibernation.
----End

5.11.2 WebUI

Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param., as shown in
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Figure
5-47.
183