UPS5000-E-(40 kVA-320 kVA)
User Manual
Set Battery capacity after repeated confirmation. Incorrect setting reduces the charging
power.
When a battery string is shared, the battery capacity of each UPS is the total capacity of
battery strings; when no battery string is shared, the battery capacity of each UPS is the
battery capacity of the single UPS.
A high or low charging power tends to shorten the battery lifespan, or even damages
batteries. If you do not know how to confirm the battery capacity, contact Huawei
technical support.
Number of cells refers to the number of 2 V cells in a single battery string connected to
the UPS. For example, if 36 batteries (150 Ah, 12 V) are connected in series to form a
battery string, and two of such battery strings are connected in parallel and then to the UPS,
set Number of cells to 216 (36 x 6) and Battery capacity to 300 Ah (150 Ah + 150 Ah).
If 192 batteries (300 Ah, 2 V) are connected in series to form a battery string, and two of
such battery strings connected in parallel and then to the UPS, set Number of cells to 192
(192 x 1) and Battery capacity to 600 Ah (300 Ah + 300 Ah). It affects the charge voltage
and discharge time. An incorrect setting will cause a high or low charge voltage, which
greatly shortens the battery lifespan. In addition, the UPS may shut down before the
batteries are fully discharged, which may lead to a data backup fault.
Step 4 If no alarm is displayed on the Monitoring screen, skip this step; if an alarm is displayed,
clear the alarm.
Step 5 Check that the bypass input is normal and the system has transferred to bypass mode. You can
confirm this by viewing the system running diagram on the LCD.
Step 6 Start the inverter.
Issue 10 (2015-09-15)
Figure 5-7 System Param. 2 screen
After you set parameters on the Settings Wizard screen, tap System Info. > Settings > Advanced
Param.. Check that System Capacity, Power module capacity, Requisite modules, and
Redundant modules match the actual values.
Tap System Info. > Settings > Dry contacts. Set the dry contacts that are used to Enabled and the
dry contacts that are not used to Disabled.
Method for starting the inverter on the LCD
a.
On the main screen, tap Common Functions. Tap Inverter On.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations