UPS5000-E-(40 kVA-320 kVA)
User Manual
4.1.3.5 Maintenance Screen
On the System Info. screen, tap
asking you to enter a user name and password. After you log in, the Maintenance screen is
displayed, as shown in
ON, Inv. OFF, ECM Switchover and Screen Calib on the Maintenance screen. You can
also perform Parallel Inv. ON and Parallel Inv. OFF for parallel systems, as shown in
Figure
Figure 4-52 Mainenance Screen (single UPS)
Figure 4-53 Maintenance Screen (parallel system)
Issue 10 (2015-09-15)
ATS
Works with the intelligent power supply device.
D.G startup batt. volt. (V/cell)
Works with the intelligent power supply device. The value range is 1.80–2.00 V/cell, and
the default value is 1.80 V/cell.
Figure
4-53.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
. If you have not logged in, a dialog box is displayed,
4-52. You can perform Battery Maint., USB Operations, Inv.
4 User Interface
132