UPS5000-E-(40 kVA-320 kVA)
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0583-1
0583-4
0583-5
0583-6
Issue 10 (2015-09-15)
Alarm
Severit
Name
y
Inter-rack
Critical
par. cable
abnormal
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
the upper
threshold.
The load
is
excessive.
1. Check the inter-rack parallel
The
system CAN bus.
inter-rack
parallel
2. Rectify the disconnection or
system
short-circuit fault.
CAN bus
3. Replace the ECM.
is
disconnec
ted or
short-circ
uited.
Only one
rack
works in a
parallel
system.
An ECM
is faulty.
The
Replace the parallel cable.
inter-rack
industrial-fre
quency
synchronizati
on cable is
broken.
The
inter-rack
carrier
synchronizati
on cable is
broken.
The
intra-rack
INVBYP
cable is
broken.
The
parallel
CAN bus
is broken.
B Alarm List