Huawei UPS5000-E-12 User Manual page 169

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power.
Before you shut down the UPS, ensure that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Issue 10 (2015-09-15)
Method for shutting down the inverter on the LCD
a.
On the main screen, tap Common Functions. Tap Inv. Off.
b.
If you have not logged in, enter a user name and password, and tap
login screen displayed.
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
c.
In the displayed dialog box, tap Yesto shut down the inverter, as shown in
5-15.
Figure 5-15 Inverter Off screen
You can also tap System Info. > Maintenanceand shut down the inverter on the Maintenance screen.
Method for shutting down the inverter on the WebUI
a.
In a web browser, enter the UPS IP address.
b.
On the login page, select a display language, enter a user name and password, and
click Login.
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
on the
Figure
160