UPS5000-E-(40 kVA-320 kVA)
User Manual
Alarm
ID
(Alarm
ID-Caus
e ID)
0565-1
0566-1
0570-4
Issue 10 (2015-09-15)
Alarm
Severit
Name
y
Load
Minor
impact
transfer-to-
bypass
Output
Minor
overload
BPM
Critical
module
abnormal
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
reduces
power module.
the rated
system
power.
The
module is
damaged.
1. Check the load.
A
large-pow
2. If the load is normal, replace the
er RCD
power module.
load is
instantly
connected
, or the
output
load
short-circ
uits.
The
inverter
bridge
short-circ
uits.
1. Check that there is no overload.
The load
is
2. Check that the module power is
excessive.
not derated due to a fan fault.
3. If the alarm persists, replace the
Derating
power module.
reduces
the rated
system
power.
The
module is
damaged.
1. Check the bypass fan and air
The
channel. If the fan is faulty,
bypass
replace it.
fan is
abnormal,
2. Check that the ambient
or the air
temperature is within 40° C.
channel is
3. Check that there is no overload.
blocked.
The
ambient
temperatu
re exceeds
B Alarm List
234