Figure 3-7 Pipe support (unit: mm)

3.1.3.5 Cables

● The onsite ground bonding resistance must comply with related standards.
● The cable flame spread rating must be at least VB.
● Select power cables with appropriate diameters based on the maximum
working currents.
When connecting cables, fit them with protective hoses.
Issue 02 (2020-08-30)
NO TE
● The height of a U-shaped pipe clamp equals the diameter of the pipe with thermal
insulation foam minus 5 mm. The pipe supports are to be purchased.
● Stainless steel 304 is recommended for pipe supports and pipe clamps.
● Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away
from each bending point in the turning section.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
33