3.2.4 Pipe Support

Figure 3-5
appearance of the supports will be different based on onsite situations.
Figure 3-5 Pipe supports (unit: mm)

3.2.5 Cables

● The site ground resistance must be less than 0.1 ohm.
● The fireproof level of the cables must be at least VB.
● The signal cables of indoor and outdoor units must be shielded cables, and the
shielding layer must be reliably grounded.
Table 3-5
them with protective hoses.
Table 3-5 Cable specifications
Application
Scenario
Equipotential
ground cable
Issue 04 (2022-11-25)
shows supports for refrigerant pipes and water pipes. The actual
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam). Pipe supports are subject to engineering procurement.
● It is recommended that pipe supports and pipe clamps be made of 304 stainless steel.
● Install a support every 1500 mm for the straight sections of pipes, and 500 mm away
from each bending point in turning sections.
NO TICE
lists the cables to be connected onsite. When connecting cables, fit
Specifications
6 mm
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
outdoor copper cable
3 System Installation
Remarks
The length is
determined based
on site survey.