NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 3-2 Layout of bottom pipe routing (2)
(1) NetCol8000-C
Figure 3-3 Layout of side pipe routing
(1) NetCol8000-C
Issue 02 (2020-08-30)
NO TE
● This installation method is not recommended for upflow units.
● The height of raised floors is greater than 800 mm (including the space occupied by
other pipes).
● L indicates the front maintenance distance, and the minimum L is 900 mm. If this
requirement cannot be met, the minimum L after front doors are removed can be 800
mm.
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
28