Name
ON/OFF via
NMS
Air conditioner
start interval
Heating function
Heating mode
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
When the function is
disallowed, the EMS is not
allowed to turn on or off
the devices.
Specifies the time interval
between the starts of units
under teamwork control.
Enable indicates that the
electric heater will be
started when the ambient
temperature is lower than
the certain temperature
range of the temperature
set point. Disable indicates
that the electric heater will
not be started. Enabled
when active power
indicates that the electric
heater will be started when
the main power is active
and the ambient
temperature is lower than
the certain temperature
range of the temperature
set point.
If Dehumidifying heating
is selected, the electric
heater starts heating based
on the current temperature
only after the
dehumidification function
is enabled. If Low-temp
heating is selected, the
electric heater starts
heating based only on the
current temperature, no
matter the
dehumidification function
is enabled or not. If
Dehumid & low-temp
heat is selected, the
electric heater starts
heating when the
dehumidification and
heating condition or the
low temperature heating
condition is met.
D Parameter Description
Default Value
Enable
2 s
Enabled when
active power
Dehumid &
low-temp heat
220