Huawei NetCol8000-C070 User Manual page 158

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alar
m ID
A280
A281
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Power
Major
1. The power supply
frequenc
frequency exceeds the
y
upper threshold.
abnormal
2. The SPD and voltage
detection board is faulty.
Power
Major
1. The power supply
frequenc
frequency is below the
y
lower threshold.
abnormal
2. The SPD and voltage
detection board is faulty.
Backup
Major
1. The power supply
power
frequency exceeds the
frequenc
upper threshold.
y
2. The voltage detection
abnormal
board is faulty.
Backup
Major
1. The power supply
power
frequency is below the
frequenc
lower threshold.
y
2. The voltage detection
abnormal
board is faulty.
Power
Major
1. The power supply
voltage
voltage exceeds the
abnormal
upper threshold.
2. The SPD and voltage
detection board is faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Check the power
supply frequency, and
ensure that it is within
the working range.
2. Replace the SPD and
voltage detection
board.
1. Check the power
supply frequency, and
ensure that it is within
the working range.
2. Replace the SPD and
voltage detection
board.
1. Check the power
supply frequency, and
ensure that it is within
the working range.
2. Replace the voltage
detection board.
1. Check the power
supply frequency, and
ensure that it is within
the working range.
2. Replace the voltage
detection board.
1. Check that the
power supply voltage
is within the operating
range.
2. Replace the SPD and
voltage detection
board.
150

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents