Figure 6-5 Removing a downflow wet film humidifier (NetCol8000-C130D)
Figure 6-6 Removing a downflow wet film humidifier (NetCol8000-C190D)
Step 8 Reinstall the wet film humidifier by performing
After replacing the wet film humidifier, properly install and secure the humidifier
water inlet pipe. Otherwise, the pipe may leak.
Step 9 On the home screen, choose Maint > Wizard Startup, and commissing the wet
film humidifier to check that the humidifier is normal. Then exit from the wizard
startup mode.
Step 10 On the home screen, choose Maint > Performance Maint to enter the
Performance Maint screen, and clear the runtime of the wet film humidifier.