NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 3-27 Connecting the downflow drainpipe
(1) Drainpipe
●
●
3.5.3.2 (Optional) Connecting the Water Inlet Pipe for the Wet Film
Humidifier
Install a water filtering device at the port of the water inlet pipe for the wet film
humidifier.
The following figure uses a rigid pipe as an example.
Figure 3-28 Water inlet pipe
●
●
Issue 02 (2020-08-30)
Port reserved in the device: 3/4 in. BSPP, port with inner screw threads.
Onsite connection: 3/4 in. BSPT, port connected to a PPR rigid pipe through
outer screw threads.
NO TICE
Port reserved in the device: G 1/2 in. port with outer threads.
Onsite connection: Connect a pipe with a G 1/2 in. port and inner threads to
the port reserved in the device. A stop valve needs to be installed at the water
Copyright © Huawei Technologies Co., Ltd.