Figure 4-4 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Air conditioner address, Enable teamwork CAN
resistor, Teamwork function and Networking mode can be set on slave smart
cooling products. Other parameters of the slave units will be modified by the
master unit synchronously.
Table 4-6 Teamwork settings
Parameter
Teamwork
group No.
Air
conditioner
address
Enable
Teamwork
CAN resistor
Issue 02 (2020-08-30)
Table 4-6
Description
Set the assigned
teamwork control
number.
Set the assigned
smart cooling product
address.
Indicates the build-out
resistor status of each
smart cooling product
in a teamwork group.
Set the parameter if
CAN network is used.
Copyright © Huawei Technologies Co., Ltd.
describes how to set the parameters.
Configuration
Principle
The number of the
teamwork controlled
group, which is the
same for all the devices
in the group.
Smart cooling product
addresses should be
different from each
other.
● Set this parameter
to No for non-
teamwork scenarios.
● For teamwork
scenarios, set this
parameter to Yes for
the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
4 Commissioning
Default
Value
1
NA
No
92