Alar
m ID
A27F
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Hot aisle
Major
1. The cables to the
2 temp/
temperature and
humid
humidity sensor are loose
sensor
or damaged.
fault
2. The temperature and
humidity sensor is faulty.
Hot aisle
Major
1. The cables to the
3 temp/
temperature and
humid
humidity sensor are loose
sensor
or damaged.
fault
2. The temperature and
humidity sensor is faulty.
Return
Major
1. The cables to the
air 4
temperature and
temp/
humidity sensor are loose
humid
or damaged.
sensor
2. The temperature and
fault
humidity sensor is faulty.
Fresh air
Major
1. The cables to the
1 temp/
temperature and
humid
humidity sensor are loose
sensor
or damaged.
fault
2. The temperature and
humidity sensor is faulty.
Return
Major
1. The cables to the
air
temperature and
damper 1
humidity sensor are loose
temp/
or damaged.
humid
2. The temperature and
sensor
humidity sensor is faulty.
fault
Return
Major
1. The cables to the
air 1
temperature and
temp/
humidity sensor are loose
humid
or damaged.
sensor
2. The temperature and
fault
humidity sensor is faulty.
Water
Critica
The water overflow
overflow
l
sensor detects water or
alarm
the sensor is faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
While configuring the
water overflow sensor,
check and clear the
water source, and
maintain or replace the
sensor.
149