Huawei NetCol8000-C070 User Manual page 101

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Parameter
Teamwork
function
Networking
mode
Number of
smart
cooling
products in
this group
Issue 02 (2020-08-30)
Description
Disable or enable the
teamwork function. If
the teamwork
function is disabled,
this device is
operating according to
its own control. If the
teamwork function is
enabled, this device
works in harmony
with others that in the
same group.
Networking mode for
the teamwork. The
networking mode set
on the screen must be
consistent with the
actual networking
mode. Otherwise, the
teamwork control
function will be
unavailable. If the
networking mode
changes, select the
corresponding
networking mode on
the screen. If the
networking mode is
changed on the
screen, the software
will restart and then
run in the new
networking mode.
(For V200R002
version, the software
will not restart when
the networking mode
is changed )
Number of the smart
cooling products in
this group (1 to 32
can be set).
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
Set this parameter
based on the onsite
device heat distribution.
Networked over CAN or
MAC_CAN. CAN
network indicates
teamwork control over
a CAN bus, MAC_CAN
network teamwork
control over an FE port.
Total number of the
smart cooling products
in this group.
4 Commissioning
Default
Value
Disable
MAC_CAN
network
3
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190