Huawei NetCol8000-C070 User Manual page 35

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 3-1 Layout of bottom pipe routing (1)
(1) NetCol8000-C
Issue 02 (2020-08-30)
During the NetCol8000-C operation, all doors and windows of the equipment
room should be closed to reduce the additional load of the smart cooling
product.
Install the NetCol8000-C in a spacious space.
The smart cooling products should be placed as far away from offices as
possible, and noise control measures should be taken.
NO TE
● The height of raised floors is greater than 500 mm for downflow units (only the space
for fan rotation, excluding the space occupied by other pipes).
● The height of raised floors is greater than 300 mm for upflow units.
● W indicates the distance between smart cooling products. The minimum W for upflow
units is 300 mm, and the minimum W for downflow units is 500 mm.
● L indicates the front maintenance distance, and the minimum L is 900 mm. If this
requirement cannot be met, the minimum L after front doors are removed can be 800
mm.