Menu
System
Settings
Issue 02 (2020-08-30)
Paramete
Description
r
Heating
Enable indicates that the
function
electric heater will be
started when the ambient
temperature is lower
than the certain
temperature range of the
temperature set point.
Disable indicates that the
electric heater will not be
started. Enabled when
active power indicates
that the electric heater
will be started when the
main power is active and
the ambient temperature
is lower than the certain
temperature range of the
temperature set point.
Heating
If Dehumidifying
mode
heating is selected, the
electric heater starts
heating based on the
current temperature only
after the
dehumidification function
is enabled. If Low-temp
heating is selected, the
electric heater starts
heating based only on
the current temperature,
no matter the
dehumidification function
is enabled or not. If
Dehumid & low-temp
heat is selected, the
electric heater starts
heating when the
dehumidification and
heating condition or the
low temperature heating
condition is met.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
Retain the default value.