NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 3-35 Equipotential bonding point of an upflow unit
(1) Equipotential bonding point
Figure 3-36 Equipotential bonding point of a downflow unit
(1) Equipotential bonding point
Step 2 Connect wiring terminals of the L1, L2, and L3 wire of the input power cable
respectively to the corresponding terminals of the external power cable.
Step 3 Connect the PE cable to the cabinet ground screw, as shown in the following
figure.
●
Issue 02 (2020-08-30)
Upflow
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
59