NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Settings >
System
Settings >
T/H sensor
Issue 02 (2020-08-30)
Name
Floor water
overflow alarm
action
In-cabinet water
overflow alarm
action
Backup power
supply
Temperature and
humidity control
type
Temperature
control mode
Temperature
setpoint
Humidity
setpoint
Return air sensor
Cold aisle sensor
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Shutdown, Inactiveity,
Only indoor fan running,
or Humidification
stopped can be set as
required.
Shutdown, Inactiveity,
Only indoor fan running,
or Humidification stopped
can be set as required.
N/A
Cold aisle, Hot aisle,
Return air, or Supply air
can be set as required. The
temperature and humidity
set points correspond to
the selected control type
can be set.
Controls the temperature
inside the room or aisles
based on the Average
valve, Max valve, or Min
valve of the temperatures
collected by each sensor.
After the Temperature and
humidity control type and
the temperature value
under this type are set, the
device conducts cooling or
heating based on the
settings.
After the Temperature and
humidity control type and
the humidity value under
this type are set, the device
conducts humidifying or
dehumidifying based on
the settings.
The return air sensors can
be set to Enable or
Disable.
The sensors in cold aisles
can be set to Enable or
Disable.
D Parameter Description
Default Value
Shutdown
Humidification
stopped
Normal
Supply air
Average value
22.0 °C
50.0 %RH
Disable
Disable
223