3.5.1 Cabinet Hole Positions
● Pipes only can be routed from the bottom of the downflow units, pipes can be
routed from the side or bottom of the upflow units. Knock off the padding of
holes at the proper positions based on the onsite pipe routing method, and
route the pipes through the holes.
● Cables can be routed from the bottom or side of the upflow units and cables
can be routed from the bottom of the downflow units. Knock off the padding
of holes at the proper positions based on the onsite cable routing method, and
route the cables through the holes.
3.5.1.1 Holes in the Side Panel of an Upflow Unit
Figure 3-20 Holes in the side panel of an upflow unit (unit: mm)
(1) Drainpipe hole
(4) Humidifier water
inlet pipe hole
(7) Standby power
cable hole
3.5.1.2 Holes at the Bottom of a Downflow Unit
Issue 02 (2020-08-30)
NO TICE
(2) Signal cable
hole
(5) Chilled water
return pipe hole
Copyright © Huawei Technologies Co., Ltd.
(3) Chilled water supply
pipe hole
(6) Mains power cable
hole